| Modello | VN-U00151SY-E | VN-U00251SY-E | VN-U00351SY-E | VN-U00501SY-E | VN-U00651SY-E | VN-U00801SY-E | VN-U01001SY-E | |||
| Portata d’aria | (ua/m/b) | m3/h | 150/95/73 | 250/145/100 | 350/210/140 | 500/300/260 | 650/390/260 | 800/480/320 | 1000/600/400 | |
| Efficienza di scambio termico (Riscaldamento) | (ua/m/b) | % | 83/84,5/85 | 80/82/84 | 81/84/87 | 79/80/80,5 | 77/78/79 | 78/84/91 | 78/80/87 | |
| Efficienza di scambio termico (Raffrescamento) | (ua/m/b) | % | 71/77,5/78 | 70/75/77 | 67/75/80 | 69/72/73,5 | 63/71/73 | 67/77/86 | 63/72/81 | |
| Efficienza di scambio entalpico (Riscaldamento) | (ua/m/b) | % | 76/81/82 | 75/78/81 | 73/80/84 | 73/75/76 | 70/74/76 | 73/80/88 | 72/75/83 | |
| Efficienza di scambio entalpico (Raffrescamento) | (ua/m/b) | % | 66/75/77 | 65/71/75 | 64/71/76 | 64/68/69 | 60/66/69 | 64/73/81 | 62/68/77 | |
| Pressione statica esterna(Modo Recupero calore) | ua | Pa | 90/43/26 | 75/30/16 | 160/57/26 | 125/45/39 | 150/58/29 | 145/53/28 | 170/60/30 | |
| Pressione statica esterna(Modo Bypass) | m | Pa | 90/43/26 | 75/30/16 | 160/57/26 | 125/45/39 | 150/58/29 | 145/53/28 | 170/60/30 | |
| Potenza assorbita (Modo Recupero calore) | ua | W | 56/35/28 | 75/39/29 | 152/59/39 | 174/60/51 | 306/96/55 | 328/114/62 | 541/151/74 | |
| Potenza assorbita(Modo Bypass) | m | W | 56/37/29 | 75/41/30 | 152/59/39 | 174/64/54 | 306/105/58 | 328/126/67 | 541/165/80 | |
| Livello di pressione sonora (Modo Recupero calore)1 | ua | dB(A) | 28/22/20 | 28/24/20 | 34/26/21 | 36/27/25 | 39/30/24 | 39/30/23 | 41/33/24 | |
| Livello di pressione sonora (Modo Bypass)1 | ua | dB(A) | 28/23/21 | 28/25/21 | 34/26/21 | 36/28/26 | 39/31/25 | 39/31/24 | 41/34/25 | |
| Dimensioni (A x L x P) | mm | 278 x 778 x 735 | 278 x 778 x 735 | 305 x 880 x 880 | 337 x 920 x 1020 | 337 x 920 x 1020 | 386 x 1130 x 1230 | 386 x 1130 x 1230 | ||
| Peso | kg | 29.00 | 29.00 | 40.00 | 47.00 | 47.00 | 63.00 | 63.00 | ||
| Diametro condotti | mm | Φ100 | Φ150 | Φ150 | Φ200 | Φ200 | Φ250 | Φ250 | ||
| Alimentazione | V-ph-Hz | 220/240-1-50 208/230-1-60 | ||||||||
| Campo temperatura di funzionamento - aria estratta2 | +5°C ÷ +40°C, 80% UR o inferiore | |||||||||
| Campo temperatura di funzionamento - aria esterna2 | -20°C ÷ +52°C 80% UR o inferiore | |||||||||
| Temperatura locale2 | -15°C ÷ +50°C, 80% UR o inferiore | |||||||||
| The specification may be subject to change without notice for purpose of improvement. | ||||||||||